back to last page

BALZERCONTROL-EB-CY-JZ(-OZ)

The slim PVC control cable with numbered cores, Cu shield for intrinsically safe circuits


Herewith you can compile your individual catalogue!
Optimized connecting cable for intrinsically safe circuits. This cable corresponds to the regulation DIN EN 60079-14. A circuit is intrinsically safe if a certain potentially explosive atmosphere, determined in harmonized standards or other generally recognized rules of technology, cannot be ignited by sparks or hot surfaces, which arise under the test conditions defined in these standards or rules. They are suitable for a voltage range of ≤ 50 V AC voltage or ≤ 75 V DC voltage. The cable is suitable for fixed installation as well as for occasionally, non-continuously recurring movement application, also in wet interiors. Outdoor use is not allowed. Due to the optimized shielding the conductor is suitable for systems where a good noise suppression is necessary and where interference of signals by electric external magnetic fields must be avoided (EMC).
  • according to BKM product specification, DIN EN 60079-14 and DIN EN 61241-14/-17
  • bare copper wire, finely stranded class 5 according to DIN EN 60228 (former DIN VDE 0295)
  • core insulation PVC TI2 according to HD 21.1
  • core colour: black with white figure printing, from 3 cores onwards with (-JZ) or without (-OZ) green/yellow core
  • cores stranded in layers, without inner sheath, wrapping in plastic foil
  • optimized screening braiding of tinned copper wires
  • outer sheath PVC TM 2 according to HD 21.1, colour blue
  • AC/DC voltage 50 V/75 V
  • test voltage 3000 V
  • transfer impedance at 30 MHz <250 Ohm/km
  • temperature range flexible application –5° C ... +70° C
  • temperature range fixed installation –40° C ... +70° C
  • minimum bending radius fixed installation 6 x outer diameter
  • minimum bending radius flexible 20 x outer diameter
  • fire behaviour according to DIN EN 60332-1-2
Number of cores x cross-section in mm² per conductor Product detail: outer diameter D in mm ca. Weight in kg/km ca. Copper weight kg/km
2 X 0.5 7.2 76 32.5
3 G/X 0.5 7.5 85 38.8
4 G/X 0.5 7.9 101 45.4
5 G/X 0.5 8.6 115 52.0
7 G/X 0.5 9.1 133 64.0
12 G/X 0.5 11.5 204 96.0
18 G/X 0.5 13.5 291 144.0
25 G/X 0.5 15.6 381 186.0
35 G/X 0.5 16.5 433 215.0
40 G/X 0.5 18.6 546 272.0
2 X 0.75 7.6 85 37.3
3 G/X 0.75 7.9 96 46.3
4 G/X 0.75 8.6 115 57.0
5 G/X 0.75 9.1 130 66.0
7 G/X 0.75 9.9 160 82.0
12 G/X 0.75 12.6 245 128.0
18 G/X 0.75 14.8 355 194.0
25 G/X 0.75 16.9 466 252.0
34 G/X 0.75 19.2 602 324.0
41 G/X 0.75 20.8 730 404.0
2 X 1.0 8.1 102 47.2
3 G/X 1.0 8.4 115 57.8
4 G/X 1.0 8.9 135 68.4
5 G/X 1.0 9.7 158 81.0
7 G/X 1.0 10.4 185 102.0
12 G/X 1.0 13.5 307 172.0
25 G/X 1.0 18.0 535 320.0
34 G/X 1.0 20.8 730 435.0
41 G/X 1.0 22.5 858 512.0
2 X 1.5 8.7 120 57.0
3 G/X 1.5 9.0 135 72.0
4 G/X 1.5 9.9 165 89.0
5 G/X 1.5 10.5 190 106.0
7 G/X 1.5 11.5 239 136.0
12 G/X 1.5 15.0 395 236.0
18 G/X 1.5 17.4 540 335.0
25 G/X 1.5 20.4 715 449.0
34 G/X 1.5 23.2 935 591.0
41 G/X 1.5 25.1 1,098 844
G/X: in your order please indicate after the article number if with protective conductor (-JZ) or without protective conductor (-OZ)
other numbers of cores on request
usual delivery design: 500 m drum